All-in-one Cabinet & Container
Battery Cabinet & Container
Hybrid Cabinet
POC Cabinet
STS Cabinet
UP-E261LP
The UP-E261LP features advanced pack-level liquid cooling and temperature balancing, maintaining cell temperature differences within 3°C. This enhances cell temperature consistency and extends battery life. Its modular design enables flexible parallel configurations and higher energy density, significantly improving the cost-ef-fectiveness, safety, and installation convenience of ESS projects.
Learn More →Learn more about America's preeminent trusted computing innovator.
1.4m²footprint only, easy transportation & fast installation.
261kWh energy in one cabinet with remarkable endurance.
Optimal in-PACK duct design, achieve high-efficient cooling and low energy consumption.
Over 8,000 times cycle life, excellent performance of battery system.
Modular design, simplified parallel expansion.
In-PACK fire warning and protection with aerosol, prevent heat diffusion and runaway.
| DC Side | |
| Cell Type | LFP/314 Ah |
| Pack Configuration | 52.2kWh/1P52S |
| System Configuration / Rated DC Voltage | 261KWh/1P260S |
| DC Voltage Range | 832V |
| Max. Charge / Discharge Rate | 0.5P |
| Max. Depth of Discharge | 100% (25±2℃) |
| AC Side | |
| Rated Output Power | 125kW |
| Max. Apparent Power | 138KVA |
| Rated AC Voltage | 230/400V |
| AC Voltage Range | ±15% |
| Grid Type | 3W+PE/3W+N+PE |
| Rated Frequency | 50Hz / 60Hz |
| Power Factor | 0.99 (adjustable -1 ~ +1) |
| THDi | ≤ 3% |
| DC Ratio | < 0.5% lpn |
| General | |
| Round Trip Efficiency | ≥89% |
| Cycle Life | ≥8,000 cycles |
| Communication | Modbus TCP/IP |
| Fire Suppression System | Aerosol |
| Ingress Rating | IP55 |
| Cooling | Forced air cooling |
| Operating Temperature | -25℃ ~ 55℃ (Derating after 45℃) |
| Anticorrosion Rating | C4 (C5 optional) |
| Humidity | 5~95%RH(non-condensing) |
| Noise | ≤ 75 dB |
| Altitude | 4000m (Derating above 2000m) |
| Dimensions (W*D*H) | 1,050*1,350*2,400mm |
| Weight | 2,600kg |
| Certification | UN38.3,IEC62477-1,IEC61000,IEC62619,IEC63056,UL9540A EN50549 |